RolinkPower ™ fully insulated intelligent ring network cabinet covers SF6 gas insulation series, solid insulation series, and environmental protection gas insulation series, And equipped with RolinkPower ™‘s intelligent power Internet of Things system truly establishes the power digital ecology of "unattended and attended".
RSAD-12 environment protection gas insulated ring network switchgear is a kind of digital ring network switchgear with environment protection materials, full insulation, full sealing, economic price and convenient operation.
All conductive parts in the mechanism are installed in a sealed stainless steel air box, with dry air as the insulation main body, the main mechanism adopts vacuum arc extinguishing, and the disconnector adopts three position structure.
The adjacent switchgear are connected by solid insulated bus.
The secondary circuit adopts integrated control technology, supports data transmission function.
Parameter | ||
---|---|---|
1 | Rated frequency/Voltage/Current | 50Hz/12kV/630A |
2 | Rated short-time withstand current | 20kA/4s |
3 | Rated power frequency withstand voltage | 42/48kV |
4 | Rated lightning impulse withstand voltage | 75/85kV |
5 | Loss category of operation continuity | LSC 2B |
6 | Internal arc grade | Arrange against the wall IAC A FL 20kA/1S Arrange from the wall IAC A FLR 20kA/1S |
7 | Protection grade of switch/cabinet | IP67/IP41 |
Environment | ||
---|---|---|
1 | Ambient temperature | -40℃~60℃(Customized below -25℃) |
2 | Relative humidity | ≦95% |
3 | Altitude | ≦4000m |
4 | Anti-seismic | Grade 8 |
5 | Especially suitable for plateau, coastal, alpine, high pollution and other areas. | |
※RSA-12 environment-protection gas insulated ring network switchgear will not have the air pressure gradually decreasing like SF6 switch at low temperature, and the insulation will continue to decline throughout the process, leading to insulation failure |
Executive standards | |
---|---|
GB 3906-2006 | 3.6kV~40.5kV AC Metal Enclosed Switchgear and Control Equipment |
GB/T 11022-2011 | Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards |
GB 3804-2004 | 3.6kV~40.5kV High Voltage AC Load Switch |
GB 1984-2014 | High Voltage AC Circuit Breaker |
GB 1985-2014 | High Voltage AC Disconnectors and Earthing Switches |
GB 3309-89 | Mechanical Test of High Voltage Switchgear at Room Temperature |
Executive standards | |
---|---|
GB 13540-2009 | Seismic requirements for high-voltage switchgear and control equipment |
GB/T 13384-2008 | General Technical Conditions for Packaging of Mechanical and Electrical Products |
GB/T 13385-2008 | Packaging Drawing Requirements |
GB/T 191-2008 | Packaging Pictorial Marks for Storage and Transportation |
GB 311.1-2012 | Insulation Coordination Part 1 Definitions, Principles and Rules |
Symmetrical design scheme is adopted for upper isolation and lower isolation. All parts required for operating mechanism and switch are universal, which shortens manufacturing cycle and facilitates quality management. The adjacent cabinets are connected by side expansion/top expansion.
1.The cable compartment can only be opened when the feeder has been isolated or grounded.
2.The bushing comply with DIN EN 50181 standard and shall be connected with M16 bolts. The arrester can be connected behind the T-shaped cable head.
3.The integrated CT is located at the bushing side, which is convenient for cable installation and is not affected by external forces.
4.The height from the bushing installation place to the ground is more than 650mm.
In case of internal arcing fault, the special pressure relief device installed at the lower part of the body will automatically start for pressure relief.
The precision transmission mechanism with reclosing function is connected by V-shaped key. The shaft support of the transmission system adopts a large number of rolling bearing design schemes, which are flexible in rotation and high in transmission efficiency, so as to ensure the mechanical life of the product more than 10000 times. The electrical components are pre designed and can be installed and maintained at any time.
Single spring double operating shaft design, built-in reliable closing, opening, grounding limit interlock device, ensure that closing and opening have no obvious overshoot. The mechanical life of the product is more than 10000 times, and the electrical components are pre designed, which can be installed and maintained at any time.
The closing and opening device with cam structure is adopted, and the dimension of over stroke and full stroke is accurate, and the production compatibility is strong. The insulation side plate adopts SMC molding process, with accurate size and high insulation strength. Three position design is adopted for closing, opening and grounding of disconnector, which is safe and reliable.
The precision transmission mechanism with reclosing function is connected by V-shaped key. The shaft support of the transmission system adopts a large number of rolling bearing design schemes, which are flexible in rotation and high in transmission efficiency, so as to ensure the mechanical life of the product more than 10000 times. The electrical components are pre designed and can be installed and maintained at any time.
Single spring double operating shaft design, built-in reliable closing, opening, grounding limit interlock device, ensure that closing and opening have no obvious overshoot. The mechanical life of the product is more than 10000 times, and the electrical components are pre designed, which can be installed and maintained at any time.
The closing and opening device with cam structure is adopted, and the dimension of over stroke and full stroke is accurate, and the production compatibility is strong. The insulation side plate adopts SMC molding process, with accurate size and high insulation strength. Three position design is adopted for closing, opening and grounding of disconnector, which is safe and reliable.
The disconnector is designed with three positions to prevent misoperation. High performance disc spring ensures the stability of contact pressure and is conducive to the design of contact with closing shape, thus ensuring the reliability of grounding closing.
The three position isolation mechanism with quick closing function is designed with single spring and two independent operating shafts to avoid misoperation.
The core unit module can be sold separately, and all parameters have been adjusted in place before delivery, so customers do not need to debug again.
The customer only needs to install the core unit module in the cabinet for set completion.
Our company provides customers with a full range of cabinet drawings, secondary schematic diagrams, product manuals, promotional materials, technical consulting and other services for free.
Intelligent switchgear manufacturing base:
Office telephone: 0519-8602-9925
Company Email: switch@rolink.com.cn
No. 101, Yong'anli Road, Luoyang Town, Wujin District, Changzhou City, Jiangsu Province
Power Supply Internet of Things Technology Research Institute:
Office telephone: 029-8114-1058
Company Email: rolinkpower@rolink.com.cn
Building B, CIC International, Jinye 1st Road, High tech Zone, Xi'an, Shaanxi