RolinkPower ™ Intelligent equipment covers power transformation and distribution automation products, power equipment online monitoring products, environmental sensors in power transformation and distribution stations Video security, electrical fire and energy efficiency monitoring. All intelligent devices can use local wireless network without charge, Ethernet or RS485 and other communication networks, connect the intelligent power cloud platform through the edge gateway, and build a complete intelligent Internet of Things energy management system.

Location:Home > Products > Electrical fire
Power transformation and distribution automation products
Online monitoring device
Environmental sensor
Video and Security
Electrical fire
Energy efficiency management

Fault arc detector

698ccd36a752ead882836961a59c6a7f.jpg
Product Overview
Product characteristics
Technical parameter
Overall dimensions

CKA10-63 fault arc detector meets the requirements of the national standard GB14287.4-2014 Electrical Fire Monitoring System - Part 4: Fault Arc Detector. It is easy to install, reliable and fully functional, and can effectively prevent electrical fires caused by fault arcs.

CKA10-63 fault arc detector is widely used in schools, hospitals, nursing homes, hotels, shopping malls, office buildings, cinemas, libraries, museums, ancient buildings, subway stations, railway stations, bus stations and other places.

CKA10-63 fault arc detector can be installed separately to protect relatively independent power consumption areas, or can be networked to form an electrical fire monitoring system.


CKA10-63 fault arc detector can accurately detect and identify series fault arc, parallel fault arc and ground fault arc in the line. The aging of lines, the damage of cable insulation, the looseness of terminal screws, and the poor internal contact of wall sockets are all prone to the occurrence of fault arcs. When the detector detects a fault arc in the lower line, it will send out an audible and visual alarm signal. At the same time, it will output an external alarm signal through the relay output contact, and upload the alarm signal to the monitoring equipment through RS485 communication.


modelCKA10-63

Rated voltage

AC220V±15%

Rated frequency

50Hz

Rated current

16A、32A、63A

Maximum power

1W

Alarm conditions

14 or more half cycle fault arcs within 1s

Alarm mode

Acousto-optic alarm

Output contact

Passive normally open type, AC250V/5A、DC30V/5A

Communication mode

RS485

Ambient temperature

-15℃~+45℃

Relative humidity

≤96%

Installation method

TH35mm standard guide rail install

Executive standards

GB14287.4-2014


微信图片_20211029200609.png

Intelligent switchgear manufacturing base:

Office telephone: 0519-8602-9925

Company Email: switch@rolink.com.cn

No. 101, Yong'anli Road, Luoyang Town, Wujin District, Changzhou City, Jiangsu Province

Power Supply Internet of Things Technology Research Institute:

Office telephone: 029-8114-1058

Company Email: rolinkpower@rolink.com.cn

Building B, CIC International, Jinye 1st Road, High tech Zone, Xi'an, Shaanxi

Consulting hotline

0519-8602-9925

WeChat Official Account